Miniature Circuit Breaker

Miniature Circuit Breaker: ZSEE B series, suitable for circuits with a rated voltage up to 400V and a rated current up to 125A, used for overcurrent protection of circuit facilities and electrical equipment in buildings and similar places. It can also be used for infrequent switching operations.

Compliance Standards

National Standards

GB 10963 “Overcurrent Protection Circuit Breakers for Household and Similar Places”

GB 14048.2 “Low-voltage Switchgear and Controlgear: Circuit Breakers”

GB 14048.3 “Low-voltage Switchgear and Controlgear: Switches, Isolators, Switch-Disconnectors, and Fuse-Combination Units”

GB 16917.1 “Residual Current Operated Circuit Breakers with Overcurrent Protection for Household and Similar Uses (RCBO)”

Environmental Conditions and Applications

  1. The installation location’s altitude does not exceed 2000m;
  2. Ambient air temperature is between -5℃ and +40℃, with the average temperature over 24 hours not exceeding +35℃;
  3. At a temperature of +40℃, the relative humidity of the air does not exceed 50%, and at lower temperatures, higher relative humidity is allowed, such as 90% at +20℃;
  4. Pollution level 2 (i.e., “non-conductive pollution under normal conditions, but temporary conductivity due to condensation has been considered”);
  5. Vertical installation with a tolerance of ±5°;
  6. Terminal devices are installed on TH35-7 type mounting rails.

Product Features

  1. Ensuring Short-Circuit Breaking Capacity
    The miniature circuit breaker product has a maximum short-circuit breaking capacity of 10kA.

  2. Ensuring Quick Disconnection
    In the event of a short circuit, the breaker can disconnect quickly without interference from power supply conditions or selective interference from instantaneous characteristic curves, ensuring the protection of personnel, electrical equipment, and circuits.

  3. Vertical Installation Stability on DIN Rails
    After the MCB is installed onto the DIN rail, the molded plastic component (mounting clip) attached to the bottom of the miniature circuit breaker improves its vertical stability, eliminating torsional stress and counteracting force on the breaker. Comparing breakers between competitors, differences in mounting clip design play a significant role.

  4. Unique Mounting Clip for Securing and Removing Miniature Circuit Breakers on DIN Rails
    The unique mounting clip allows for both normal fastening on the DIN rail and easy removal of the miniature circuit breaker from a row of devices without needing to disconnect the entire connection circuit.

Other features: The clip does not detach from the main body of the miniature circuit breaker, and no additional accessories such as stainless steel springs are required.

  1. Strong Terminal Positioning
    After riveting, the terminal can move freely up and down. There is a good locking mechanism for the torque of the screw, preventing the terminal post from rotating arbitrarily. When the terminal screw is loosened, it will not fall out of the housing.

  2. Terminals Can Accommodate Large Cross-Sectional Wires
    Solid wires with a cross-sectional area of 25mm² and stranded wires with a cross-sectional area of 16mm² can carry a current of up to 63A. When installing large cross-sectional wires for high-current input, additional terminals are not required.

Tripping Types

Instantaneous Tripping Types for Miniature Circuit Breakers Tripping Current Range
B 3In~5In
C 5In~10In
D 10In~20In

ZSEEB1 Series Miniature Circuit Breakers

Model Description

Example of selection: ZSEE B1-63/3 C 16

ZSEE, miniature circuit breaker, rated short-circuit breaking capacity Icn = 10kA, frame size rated current Inm = 63A, three poles, instantaneous tripping type C, rated current In = 16A.

Technical Specifications

Functional Features

  1. Precision bimetal thermal overload tripping device for time-delayed protection of circuits;
  2. Electromagnetic solenoid high-speed tripping device for short-circuit protection of circuits;

Prevents overloading of the distribution system (in cases where no short-circuit fault occurs but there is a risk of overheating that could damage wires and cables);
Prevents short circuits in the distribution system and electrical devices (e.g., faults caused by circuit errors or incorrect connections).

External Dimensions (mm)

ZSEEB1-63 Series Circuit Breaker Accessories

Model Name U3+O3 Over/Under Voltage Tripping Device F3 Auxiliary Switch SD3 Alarm Switch S3+F3 Shunt + Auxiliary Tripping Device
Appearance
U3+O3
F3
SD3
S3+F3
Rated Voltage (Ue) AC 230V
Working Voltage Range 70~100% Us 70~100% Us 70~100% Us
Rated Control Voltage (Us) AC400/230V DC130/48/24V AC/DC110V~400V (no note)
AC/DC24V~48V (needs notation)
Rated Insulation Voltage (Ui) 500V 500V 500V 500V
Insulation Strength 2000V/min 2000V/min 2000V/min 2000V/min
Overvoltage Tripping Range 280V ±5%
Undervoltage Tripping Range 170V ±5%
Mechanical Electrical Life 100,000 times 100,000 times 100,000 times 100,000 times
Contact Capacity AC: 3A/415V
DC: 1A/130V
AC: 6A/240V
DC: 2A/48V
DC: 6A/24V
AC: 3A/400V
DC: 1A/130V
AC: 6A/230V
DC: 9A/125V
AC: 3A/400V
DC: 1A/130V
AC: 6A/230V
DC: 9A/125V
Installation Position Left Left Left Left
Width 18mm 9mm 9mm 18mm
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Functional Role Does not automatically trip in case of over/undervoltage Indicates ON/OFF status of the related circuit breaker Used to connect ON/OFF auxiliary contacts, tripping indicator shows breaker is off Remote control automatic tripping of ZSEEB1

ZSEEB2 Series Miniature Circuit Breakers

Model Description:

Selection Example:

ZSEEB2-63/4D16

ZSEE, miniature circuit breaker, rated short-circuit breaking capacity Icn=6kA, frame rated current Inm=63A, four poles, instantaneous tripping type D, rated current In=16A.

ZSEEB2-32/ C32

ZSEE, miniature circuit breaker, frame rated current Inm=32A, 1P+N, instantaneous tripping type C, rated current In=32A.

Note: For 32-frame products, the number of poles 1P+N is not marked by default.

Technical Specifications

Functional Features

  1. Precise bimetallic thermal overload trip unit provides delayed protection for the circuit;
  2. Electromagnetic high-speed trip unit with solenoid for short-circuit protection;

Prevents distribution system overload (in case no short-circuit fault occurs, but overheating overload situations that may damage the wiring arise); Prevents short-circuits in the distribution system and electrical devices (such as faults caused by wiring errors or other circuit failures).

Dimensions (mm)

ZSEEB2-63 Series Circuit Breaker Accessories

Model Name OUV2 Over/Under Voltage Trip Unit F2 Auxiliary Switch SD2 Alarm Switch MXF2 Shunt+Auxiliary Trip Unit
Appearance
OUV2
F2
SD2
MXF2
Rated Operating Voltage (Ue) AC 230V AC 415/240V
DC 130/48/24V
AC 415/240V
DC 130/48/24V
AC 230V / DC 24V
Operating Voltage Range 70~100% Us 70~100% Us
Rated Control Voltage (Us) AC 400, 230, 115V AC/DC 110V~400V (not marked)
AC/DC 24V~48V (marked)
Rated Insulation Voltage (Ui) 500V 500V 500V
Insulation Strength 2000V/min 2000V/min
Overvoltage Trip Range 280V ±5%
Undervoltage Trip Range 170V ±5%
Mechanical Electrical Life 100,000 times 100,000 times 100,000 times 100,000 times
Contact Capacity AC: 3A/415V
AC: 6A/240V
DC: 1A/130V
DC: 2A/48V
DC: 6A/24V
AC: 3A/415V
AC: 6A/240V
DC: 1A/130V
DC: 2A/48V
DC: 6A/24V
AC: 3A/400V
AC: 6A/230V
AC: 9A/125V
Installation Position Left Left Left Left
Width 18mm 9mm 9mm 18mm
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Function Automatically trips under overvoltage or undervoltage conditions Indicates “off” and “on” status of the associated breaker Auxiliary contact, indicates breaker open status when tripped, for ON/OFF connection Combines the functions of auxiliary switch and shunt trip unit

Note: For ZSEEB2 series breakers, up to 2 accessories can be installed on the left side.

ZSEEB2S Series Miniature Circuit Breakers

Model Description

Selection Example:

ZSEEB2S-63/4D16
ZSEE, miniature circuit breaker, rated short-circuit breaking capacity Icn=6kA, frame rated current Inm=63A, four poles, instantaneous tripping type D, rated current In=16A.

Technical Specifications

Functional Features:

  1. Precise bimetallic thermal overload trip unit provides delayed protection for the circuit;
  2. Electromagnetic high-speed trip unit with solenoid for short-circuit protection;
    • Prevents distribution system overload (in case no short-circuit fault occurs, but overheating overload situations that may damage the wiring arise);
    • Prevents short-circuits in the distribution system and electrical devices (such as faults caused by wiring errors or other circuit failures).
  3. The breaker has a high short-circuit breaking capacity;
  4. When the breaker trips due to overcurrent, the handle moves to the off position, prompting users to quickly address the fault.

Dimensions (mm)

ZSEEB2S-63 Series Circuit Breaker Accessories

Model Name OUV1 Over/Under Voltage Trip Unit F1 Auxiliary Switch SD1 Alarm Switch MXF1 Shunt+Auxiliary Trip Unit
Appearance
OUV1
F1
SD1
MXF1
Rated Operating Voltage (Ue) AC 230V
Operating Voltage Range 70~100% Us 70~100% Us
Rated Control Voltage (Us) AC 400, 230, 115V AC/DC 110V~400V (not marked)
AC/DC 24V~48V (marked)
Rated Insulation Voltage (Ui) 500V 500V 500V
Insulation Strength 2000V/min 2000V/min
Overvoltage Trip Range 280V ±5%
Undervoltage Trip Range 170V ±5%
Mechanical Electrical Life 100,000 times 100,000 times 100,000 times 100,000 times
Contact Capacity AC: 3A/415V
AC: 6A/240V
DC: 1A/130V
DC: 2A/48V
DC: 6A/24V
AC: 3A/415V
AC: 6A/240V
DC: 1A/130V
DC: 2A/48V
DC: 6A/24V
AC: 3A/400V
AC: 6A/230V
AC: 9A/125V
Installation Position Right Left Left Right
Width 18mm 9mm 9mm 18mm
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Wiring Diagram
Function Automatically trips under overvoltage or undervoltage conditions Indicates “off” and “on” status of the associated breaker Auxiliary contact, indicates breaker open status when tripped, for ON/OFF connection Combines the functions of auxiliary switch and shunt trip unit

Note: ZSEEB2S series circuit breakers can install up to 2 accessories.

ZSEEB1L Series Miniature Circuit Breakers with Residual Current Protection

Model Description

Example of model selection: ZSEEB1L-63/4C16 30mA

ZSEE, miniature circuit breaker with residual current protection, rated short-circuit breaking capacity Icn=10kA, frame rated current Inm=63A, four poles, instantaneous trip type C, rated current In=16A, residual operating current 30mA.

Technical Specifications

Features

  1. Provides four protections: leakage, isolation, short-circuit, and overload;
  2. Offers personal protection against indirect contact;
  3. Provides supplementary protection against direct contact;
  4. Protects electrical equipment from insulation failures;
  5. Suitable for circuits with AC 50Hz or 60Hz, rated voltage 230V/400V, and rated current not exceeding 63A. Mainly used for personal protection against electric shocks, overcurrent and short-circuit protection for buildings and similar installations, and fire risk protection due to ground fault currents caused by insulation damage of electrical equipment;
  6. Circuit breakers are suitable for various applications, including industrial, commercial, high-rise, and residential buildings.

Dimensions (mm)

Dimensions table (mm)

Poles 1P+N 2P 3P 3P+N 4P
L(Inm≤32A) 45 63 90 99 117
L(Inm>32A) 54 72 103.5 117 135
H 76.8 77.8 77.8 77.8 77.8

ZSEEB2L Series Miniature Circuit Breakers with Residual Current Protection

Model Description

Example of model selection: ZSEEB2L-63/4C16 30mA

ZSEE, miniature circuit breaker with residual current protection, rated short-circuit breaking capacity Icn=6kA, frame rated current Inm=63A, four poles, instantaneous trip type C, rated current In=16A, residual operating current 30mA.

Technical Specifications

Features

  1. Provides four protections: leakage, isolation, short-circuit, and overload;
  2. Offers personal protection against indirect contact;
  3. Provides supplementary protection against direct contact;
  4. Protects electrical equipment from insulation failures;
  5. Suitable for circuits with AC 50Hz or 60Hz, rated voltage 230V/400V, and rated current not exceeding 63A. Mainly used for personal protection against electric shocks, overcurrent and short-circuit protection for buildings and similar installations, and fire risk protection due to ground fault currents caused by insulation damage of electrical equipment;
  6. 32A and 40A frame products can disconnect both the live and neutral lines simultaneously;
  7. Circuit breakers are suitable for various applications, including industrial, commercial, high-rise, and residential buildings.

Dimensions (mm)

Dimensions table (mm)

Poles 1P+N 2P 3P 3P+N 4P
L(Ie≤32A) 45 63 90 99 117
L(Ie>32A) 54 72 103.5 117 135
H 76.8 77.8 77.8 77.8 77.8

ZSEEB2SL Series Miniature Circuit Breakers with Residual Current Protection

Model Description

Example of model selection: ZSEEB2SL-63/4C16 30mA

ZSEE, miniature circuit breaker with residual current protection, rated short-circuit breaking capacity Icn=6kA, frame rated current Inm=63A, four poles, instantaneous trip type C, rated current In=16A, residual operating current 30mA.

Technical Specifications

Features

  1. Provides four protections: leakage, isolation, short-circuit, and overload;
  2. Offers personal protection against indirect contact;
  3. Provides supplementary protection against direct contact;
  4. Protects electrical equipment from insulation failures;
  5. Suitable for circuits with AC 50Hz or 60Hz, rated voltage 230V/400V, and rated current not exceeding 63A. Mainly used for personal protection against electric shocks, overcurrent and short-circuit protection for buildings and similar installations, and fire risk protection due to ground fault currents caused by insulation damage of electrical equipment;
  6. Circuit breakers are suitable for various applications, including industrial, commercial, high-rise, and residential buildings.

Dimensions (mm)

ZSEEB3SL Series Miniature Circuit Breakers with Residual Current Protection

Model Description

Example of model selection: SIW B3SL-32/ C 16 30mA

ZSEE, miniature circuit breaker with residual current protection, rated short-circuit breaking capacity Icn=4.5kA, frame rated current Inm=32A, 2P, instantaneous trip type C, rated current In=16A, residual operating current 30mA.

Technical Specifications

Dimensions (mm)

ZSEEG3 Series Isolating Switches

Model Description

Example of model selection: ZSEE G3-125/4Ie=100

ZSEE, isolating switch, rated heating current Ith=125A, four poles, rated current Ie=100A.

Technical Specifications

Features

  1. Locking function for on and off positions;
  2. Contact status indicator for open and closed positions;
  3. High rated making capacity;
  4. High short-time withstand current;
  5. Mainly used as the main switch for terminal combined electrical appliances.

Dimensions (mm)

ZSEEB-GQ Series Self-Resetting Over/Under Voltage Protectors

Application Range

Self-resetting over/under voltage protectors are suitable for AC voltage 230V or 380V, frequency 50Hz, and rated working current of 63A or less. They provide protection for electrical equipment against over/under voltage caused by neutral line faults in single-phase or three-phase circuits, such as in distribution circuits for residential meter boxes.

Model Description

Example of model selection: ZSEEB-GQ-32/2

ZSEE, self-resetting over/under voltage protector, rated working current In=32A, two poles.

Technical Specifications

Features

  1. Cuts off the circuit when undervoltage occurs, and automatically resets and reconnects the circuit after the voltage returns to normal with a delay, without manual operation;
  2. The protector does not misoperate during transient or temporary overvoltage in the circuit;
  3. The protector does not connect the circuit when the voltage is unstable due to poor contact or in cases of sudden power loss and restoration;
  4. The protector exhibits an inverse time characteristic with an action time of ≤1s;
  5. Wiring method: Bottom entry and top exit. (*Note: For top entry and bottom exit, please contact the company’s marketing department.)

Dimensions (mm)

For more information, you can contact us via email:[email protected], Click here for more contact details
Next
Previous